Module insertion type ultrasonic flowmeter
The host is small, the function is complete, the price is low, the use of rail installation, suitable for batch use installation and instrument box or distribution cabinet
Selection of different types of sensors, suitable for diameter DN50~DN6000mm. without water can be installed
working environment:
Host | sensor | |
Protection class | IP30 | IP68 |
humidity | ≤85%RH | |
temperature | -20℃~60℃ | -30℃~160℃ |
Basic parameters
Accuracy | ±1% |
Flow rate range | 0~±10m/s,Positive and negative measurements |
Pipe diameter | DN50~DN6000 |
Fluid temperature | -30℃~160℃ |
Fluid type | Water, sea water, sewage, acid and alkali, alcohol, beer, all kinds of oil can carry a single uniform ultrasonic liquid |
Pipe material | Steel, stainless steel, cast iron, copper, PVC, aluminum, fiberglass, etc. All dense pipes, |
Signal output | 1 channel 4 ~ 20mA current output impedance 0 ~ 1k, accuracy 0.1% 1 channel OCT pulse output pulse width of 6 ~ 1000ms 1 relay output |
signal input | 3-way 4 ~ 20mA current input, connected 3-wire PT100 platinum resistance, to achieve heat measurement |
Communication Interface | Isolated RS485 serial interface, support MODBUS protocol |
Power supply | DC8~36V or AC85~264V |